Laserfiche WebLink
LO MAL <br /> Y` 1. <br /> TANK-TEK ENVIRONMENTAL CORPORATION <br /> APR 012016 <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> Date: 312312om Work Order# 16032302-7 <br /> Location: VALLEY PACIFIC CARDLOCK#152 Contact: M/KE EL/ASON <br /> 930 E VICTOR ROAD <br /> LODI CA 95240 Telephone: (209)948.9412 <br /> SUMP# 112 112 112 112 <br /> PRODUCT T6 87 T7 87 T6 87 T787 <br /> LD TYPE M echanlcal, OMPLLD, (P)LLD I M M M M <br /> LD MANUFACTURER VMI VMI VMI VMI <br /> LD MODEL LD2000 LD2000 LD2000 LD2000 <br /> LD SERIAL NUMBER 15021137 07031410 15021137 07031410 <br /> SUMP CONDITION DRY DRY DRY DRY <br /> RESILIENCY 150 ML 150 ML 150 ML 150 ML <br /> OPERATING PRESSURE 25 PSI 25 PSI 25 PSI 25 PSI <br /> OPENING TIME 4 SEC 4 SEC 4 SEC 3 SEC <br /> METERING PRESSURE 10 PSI 10 PSI 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 22 PSI 22 PSI 22 PSI 22 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? YES YES YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? NIA NIA NIA N! <br /> LD PASS OR FAIL? PASS PASS PASS PASS <br /> Comments: <br /> SECOND SET OF TESTS ARE DUE TO REMOVAL OF LEAK DETECTORS FOR PRECISION UNE TESTING. <br /> VERIFIED FUNCTION AND 3 GPH LEAK RATE AFTER REINSTALLATION OF BOTH AND PASSED <br /> Technician: RICHARD THOMAS Contractor Lic. # 803705 <br /> Signature: <br /> PO BOX 5850,RIVERSIDE,CA92517-5850 TEL951-779-4999 FAX 951-788-7089 <br /> W W CTANK-TEr-COM <br />