Laserfiche WebLink
January 25 , 1990 <br /> Mr. Don Keller <br /> KELLER TRUCKING <br /> 11950 North Highway 99 Site: 930 East Victor Road <br /> Lodi, California 95240 Lodi, California <br /> Dear Mr. Keller: <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate <br /> governmental agency. <br /> A tank system is considered tight, according to the <br /> current rules, if the gain/loss is less than . 05 gallons per <br /> one hour of testing. If the results are beyond these <br /> parameters, you should consider taking some remedial action. <br /> TANK ff OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Shop 300 Waste Oil +.00546 Yes <br /> South 10, 000 Diesel -.027 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> �k <br /> Frank Kese <br /> Certified ter <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />