Laserfiche WebLink
i • <br />f 'f� <br />INVOICE #AT000023 - �:;f:l TEST DATE: 07/31/94 <br />AFFORDA-TE$T <br />PO BOAC 36 <br />THORNTON, CA. 95686 <br />(209)794-2470 or (800)524-9087 <br />TANK STATUS EVALUATION REPORT <br />----------------------------- <br />***** CUSTOMER DATA ***** <br />D H WINN TRUCKING <br />19555 TULLY ROAD <br />POB 24 <br />LOCKEFORD CALIF <br />95237 <br />CONTACT: RUSS - OFFICE MANAGER <br />PHONE #: 209 727--5531 <br />***** SITE DATA ***** <br />D H WINN TRUCKING <br />19555 TULLY ROAD <br />POB 24 <br />LOCKEFORD CALIF <br />95237 <br />CONTACT: RUSS - OFFICE MANAGER <br />PHONE #: 209 727-5531 <br />***** COMMENT LINES ***** <br />CURRENT EPA STANDARDS DICTATE <br />THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br />OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br />TANK #1: DIESEL FUEL 2 TYPE: STEEL RATE: .034695 G.P.H. GAIN <br />TANK IS TIGHT. <br />d1TL A�L�11-�1' <br />OPERATOR: SIGNATURE:�jjft! DATE: _l, <br />---- 3 <br />---------- 7_ .1-- <br />