Laserfiche WebLink
Spill Bucket Testing Report Form <br /> JUN 10 2Q.rRCB,January 2006 <br /> This form is intended for use by contractors performing annual testing of UST spill containniotl pu N .11h�completed form and <br /> printouts from tests(if applicable), should be provided to the facility owner/operator for suMtttal to the local regulatory agency. <br /> 1. FACILITY INFORMATION <br /> Facility Name: ALPHA FAST GAS Date of Testing: 4-21-2016 <br /> Facility Address: 2358 WATERLOO RD <br /> Facility Contact: JIMMY Phone: <br /> Date Local Agency Was Notified of Testing 3-28-16 <br /> Name of Local Agency Inspector(ifpresent during testing): FATINA <br /> 2.TESTING CONTRACTOR INFORMATION <br /> Company Name: AFFORDA TEST 416 2nd Street Galt,CA 95632 (209)744-0112 Fax:(209)744-0116 <br /> Technician Conducting Test: ❑Lyle D.Nimmo ❑ Zane A.Nimmo ® David A.Winkler ❑ Felix G.Ramirez <br /> 5249115-UT 5263322-UT 5263373-UT 5273934-UT <br /> Credentials': ® ICC Service Tech. ®SWRCB Tank Tester <br /> 3. SPILL BUCKET TESTING INFORMATION <br /> Test Method Used: ®Hydrostatic ❑ vacuum ❑Other <br /> Test Equipment Used: h20 and tape measure Equipment Resolution: 1/16 <br /> Identify Spill Bucket(By Tank 1 87 2 91 3 DSL 4 <br /> Number, Stored Product, etc. <br /> ® Direct Bury ®Direct Bury ®Direct Bury ❑Direct Bury <br /> Bucket Installation Type: ElContained in El Contained in <br /> El Contained in Sump El in Sump Sum Sum <br /> Bucket Diameter: 1 I 11 11 <br /> Bucket Depth: 12 12 15.50 <br /> Wait time between applying <br /> vacuum/water and start of test: <br /> Test Start Time(Ti): 9 9 9 <br /> Initial Reading(RI): 11 11 14.50 <br /> Test End Time(TF): 10 10 10 <br /> Final Reading(RF): 11 11 14.50 <br /> Test Duration(TF—Ti): IHR 1HR IHR <br /> Change in Reading(RF-Ri): 0 0 0 <br /> Pass/Fail Threshold or 1/16 1/16 1/16 <br /> Criteria: <br /> Test Result: 1 ® Pass ❑Fail ® Pass ❑Fail ® Pass ❑Fail ❑ Pass ❑ Fail <br /> Comments—(include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING <br /> I hereby certify that all the information contained in this report is true,accurate,and in full compliance with legal requirements. <br /> Technician's Signature: V &— Date 4-21-16 <br /> ' State laws and regulations do not currently require testing to be performed by a qualified contractor.However,local requirements <br /> may be more stringent. <br />