Laserfiche WebLink
VITTS6 <br /> Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> 1S. WWW ^Vj TEST RESULTS <br /> 111333 1�'1 November 19 , 1987 <br /> EClVIROME?+TAI HEALTH <br /> FE4S;1lT/��R�.!lCES <br /> Don ' s Distributing Co. <br /> 1320 West Weber Ave. <br /> Stockton, California <br /> Dear Mr. Keller , <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and grnplin gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tnnk system is considered tight , according to tite current <br /> rules , if the gain is less than .02 or the loss is lens thnn . 09 <br /> gn .11nns per one hour of testing. If the results nre beyond Chum <br /> parameters , you should consider taking some remedial action. <br /> TANK A / TANK PRODUCT TEST WITHIN TIGUt' <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARANE'J'ERS <br /> North Tank <br /> Test One 3 ,000 Gasoline -. 1735 No <br /> During this test I kept noticing that the ground around the fill & <br /> Phase One Vapor was getting wet. Eventhough I had dried it prior to <br /> starting the test. I attempted to tighten both,, lines , but the small <br /> opening would not allow proper leverage. Please note the sketch & the <br /> comments on the reverse side of the worksheets . <br /> Test Two 3,000 Gasoline -. 01,376 Yes <br /> Please contact us if you need additional assistance or <br /> Information. <br /> Sincerely, <br /> WCecEifie�a�eater <br /> 800 262 TEST i 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />