Laserfiche WebLink
_ LDT 5000 Field Test Apparatus <br />Tanknology Line Leak Detector Test <br />Work Order: <br />Site Name / ID <br />Address: <br />City: <br />2337991 <br />7 -ELEVEN #17647, MKT 2368 (N-744) / 17647 <br />1048 W. YOSEMITE AVE na EL PORTEL <br />MANTECA <br />Page 1 of 1 <br />Date: 7/17/2018 <br />State: CA Zip: 95336 <br />Tank ID <br />T-1 <br />T-2 <br />Product <br />RUL <br />PUL <br />Product Line <br />1 <br />1 <br />Tested From <br />3 <br />3 <br />Existing/New <br />Existing <br />Existing <br />Mechanical/Electronic <br />Mechanical <br />Mechanical <br />Manufacturer/Model <br />Veeder Root FX1V <br />Veeder Root FX1V <br />Serial No. <br />11002 6195 116056 <br />40710 4609 11605 <br />Pump Operating Pressure (psi) <br />30.00 <br />30.00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189.0 <br />Calibrated Leak (gph) <br />3.00 <br />3.00 <br />Holding PSI <br />'NIA for Electronic Lo's <br />30.00 <br />29.00 <br />Resiliency (ml) <br />`N/A for Electronic LD's <br />180.00 <br />125.00 <br />Metering PSI <br />'NIA for Electronic Lo's <br />10 <br />10 <br />Opening Time (sec) <br />'N/A for Electronic Lo's <br />4 <br />5 <br />Test Results <br />Pass <br />Pass <br />Technician Comments: <br />Technician Name: Tim Elebeck <br />Technician Signature <br />Environmental Compliance for Petroleum Systems <br />© 2018 Tankndogy Inc., Austin, TX. All rights reserved. tanknology.wm <br />Certification #: 118337 <br />Expire Date: 5/24/2021 <br />