Laserfiche WebLink
1115000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2337991 Date: 7/17/2018 <br /> Site Name/ID: 7-ELEVEN#17647, MKT 2368(N-744)/ 17647 <br /> Address: 1048 W.YOSEMITE AVE @ EL PORTEL <br /> City: MANTECA State: CA Zip: 95336 <br /> Tank ID T-1 T-2 <br /> Product RUL PUL <br /> Product Line 1 1 <br /> Tested From 3 3 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical <br /> Manufacturer/Model Veeder Root FX1V Veeder Root FX1V v <br /> Serial No. 11002 6195 116056 40710 4609 116056 <br /> Pump Operating Pressure(psi) 30.00 30.00 r7 I, <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 30.00 29.00 <br /> 'N/A for Electronic Lo's <br /> Resiliency(ml) 180.00 125.00 <br /> N/A for Electronic Lo's <br /> Metering PSI 10 10 <br /> N/A for Electronic LD's <br /> Opening Time(sec) 4 5 <br /> NIA for Electronic Lo's <br /> Test Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Tim Elebeck Certification#: 118337 <br /> Technician Signature: `x "y f t°Ilk Expire Date: 5/24/2021 <br /> Environmental Compliance for Petroleum Systems <br /> ©2018 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />