Monitoring System Certification �l�/C <br /> � <br /> A Results of Testing/Servicing <br /> Software Version Installed: 5.00 <br /> Complete the following checklist: <br /> ❑O Yes ❑ No* Is the audible alarm operational? <br /> ❑O Yes ❑ No* Is the visual alarm operational? <br /> ❑X Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ❑O Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br /> ❑O N/A operational? <br /> 91 Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate <br /> positive shut-down? (Check all that apply) 0 Sump/Trench Sensors; ❑O Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failureldisconnection? 0 Yes; ❑No. <br /> ❑ Yes .❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br /> D N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fill point(s) and operating roerl ? :If so,at what percent of tank capacity does the alarm trigger? _% <br /> El Yes* ❑ No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> O Yes* ❑ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ❑O Water. If yes,describe causes in Section E,below. <br /> ❑x Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> El Yes ❑ No* Is all monitoring equipment oerational per manufacturer's specifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: I reprogrammed the output relays to properly recognize sump and pan sensors for_ <br /> positive shut-down and fail safe <br /> Removed less than 1 gal of rain water from the 87 sump <br /> IJN-036-2/4 Page 2 of 4 Rev.06/04/01 <br /> www.unidocs.or� <br />