Laserfiche WebLink
Vmi <br /> Vaporless Manufacturing, Inc. <br /> Quality Petroleum Equipment <br /> Solutions for Over 20 Years <br /> LDT- 890 Test Form &VMI Warranty Checklist <br /> October 1 2006 <br /> Test Information <br /> Date: 04/23/08 Test Company: EPIC Compliance Systems, Inc. <br /> Telephone: (888) 777-EPIC Contact/Technician: Alvin L. Milburn <br /> Site I.D: Gas Depot Address: 824 E. Yosemite Ave <br /> City: Manteca State: CA Zip: 95336 <br /> Type of Test Equipment: <br /> Submersible Pump Identification <br /> MFG: RED JACKET Model No: P 75 S1 Serial No: <br /> Leak Detector Identification <br /> MFG: (LD 2000) VM1 Model No: LD-2000 Serial No: 36667 <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1. Type of Pipe: FG 2. Diameter of Pipe: 2 3. Length of Pipe: 100 <br /> 4. Burial Depth of Leak Detector: 3' 5. Kind of Fuel: 91 6. Date of Last Line Test: <br /> Test Conditions <br /> 1. Operating Pump Pressure: 25 psi 2. Gallon per hour test rate: 3 @ 10 psi <br /> 3. Static Line Pressure (Pump Off): 25 psi 4. Bleedback Test(Pump Off): 150 ml. <br /> 5. Step-through time to full flow 2 seconds (0 psi. to full pump pressure, no leak) <br /> 6. Leak detector stays in Leak Search Position with a 3 GPH leak -Yes: X PASS No: FAIL <br /> 7. Was the leak detector adjusted–Yes: No: X <br /> Symptoms <br /> 1. Won't find 3 GPH leak: 2. Stays in Slow Flow: _ <br /> 3. Other: __— <br /> ************ If This Unit Is Returned Under Warranty Please Complete The Following *********** <br /> Vaporless RGA#: Return By (Company): <br /> Telephone: Contact: <br /> Customer Control #: Address: <br /> City: _- State: Zip: <br /> (See Website -www.vaporiess.com -Technical Bulletin 032805) <br />