• SWRCB,January 2002 • • Page_of_ <br /> 7. UNDER-DISPENSER CONTAINMENT C TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: INCON Equipment Resolution:.0001 <br /> UDC#3/4 UDC#7/8 UDC# UDC# <br /> UDC Manufacturer: Unk Unk <br /> UDC Material: Fiber Fiber <br /> UDC Depth: 24" 24" <br /> Height from UDC Bottom to Top 10" 10" <br /> of Highest Piping Penetration: FEB 2 2014 <br /> Height from UDC Bottom to 12" 12" <br /> Lowest Electrical Penetration: ENVIROMMEW <br /> Condition of UDC prior to Clean/Dry Clean/Dry HEALTH 0 EPARTMENT <br /> testing: <br /> Portion of UDC Tested' 18" 18" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No ❑NA ❑Yes ❑No DNA ❑Yes ❑No DNA ❑Yes ❑No DNA <br /> product and water)?* <br /> Turbine shutdown response time <br /> Is system programmed for fail- p Yes 0 No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA 0 Yes ❑No DNA <br /> safe shutdown?' <br /> Was fail-safe verified to be ❑Yes 0 No ❑NA ❑Yes O No ❑NA ❑Yes ❑No [INA ❑Yes ❑No [INA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and <br /> starting test <br /> Test Start Time: 1207 1241 <br /> Initial Reading(R1): 6.0189 4.9976 <br /> Test End Time: 1222 1256 <br /> Final Reading(RF): 6.0190 4.9971 <br /> Test Duration: 15 min 15 min <br /> Chane in Read' (RF-Ri): .0001 .0005 <br /> Pass/Fail Threshold or Criteria .002 .002 <br /> _ <br /> Was sensor removed for testing? I ❑Yes d No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and 11 Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No DNA ❑Yes ❑No ❑NA <br /> verified functional atter testing? <br /> Comments— (include information on repairs made prior to testing and recommendedfollow-up for failed tests) <br /> ' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />