INVOICE #WC000945 USTest 2000 / P TEST DATE: 04/19/98 <br /> CHAMPION PRECISION TANK TESTING <br /> P.O. BOX 13059 <br /> SACRAMENTO CA 95813-3059 <br /> TANK STATUS REPORT -- ULLAGE TEST <br /> --------------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> POSDEF POWER COMPANY POSDEF POWER COMPANY <br /> ' 2526 WEST WASHINGTON STREET 2526 WEST WASHINGTON STREET <br /> PORT OF STOCKTON PORT OF STOCKTON <br /> STOCKTON, CA. STOCKTON, CA. <br /> 95203 95203 <br /> 1 <br /> CONTACT: ED STOCKTON CONTACT: ED STOCKTON <br /> PHONE # : 209-467-3838 PHONE # : 209-467-3838 <br /> ***** COMMENT LINES ***** <br /> ULLAGE TEST ON THE ANNULAR SPACE OF THE 1000 GALLON TANK <br /> ON JOB #000944 .ANNULAR SPACE DRY FOR THE TEST. <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE THRESHOLD RATE <br /> OVER THE PERIOD OF ONE HOUR IS .05 GALLONS . <br /> IABOVE STATEMENT N/A FOR THE ULLAGE TEST.MAXIMUM SN: IS +/- 2 . 0 <br /> TANK #1 : WASTE TYPE: STEEL SN: <br /> OIL <br /> TANK IS NOT TIGHT <br /> ----------------------- <br /> ANNULAR SPACE WOULD NOT MAINTAIN PRESSURE LONG <br /> ENOUGHT TO RECORD DATA.PRESSURE WOULD DROP TO ZERO <br /> WITHIN SECONDS . PRIMARY TANK TESTED TIGHT.THERE IS <br /> ' WATER IMPUT TO THE ANNULAR SPACE. <br /> r OPERATOR: SIGNATURE : - DATE: a� - <br /> � 11114tn '4+__ <br />