Laserfiche WebLink
AFF©RDA-TEST 209 794 0112 P. 02 <br /> i • <br /> INVOICE #►78000529 TEST DATE: 01/23/0 <br /> AFFORDA-TE$T <br /> FOB 36 -- 26515 N SACRAMENTO BL <br /> THORNTON, CA 95686-0036 <br /> (209)794-0102 FAX (209)794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> STOCKTON SVC STA EQUIP CO INC PG & E <br /> P.O.B. 508 4040 N. WEST LANE <br /> @ BOURBON ST. <br /> STOCKTON, CA. STOCKTON, CA. <br /> 95201 <br /> CONTACT: JONES, MIKE <br /> PHONE #: (209)464-8333 <br /> ***** COMMENT LINES ***** <br /> 01211 10K STDW TANKS - RUL & DIESEL, TESTTIMES 90 MIN. <br /> PRESSURE SYSTEM - BALANCED VR - VEEDER-ROOT TLS--350 ATG <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND FUEL TANKS, THE <br /> THE MAXIMUM ALLOWABLE HOURLY LEAK/GAIN RATE IS .05 GALLONS. <br /> ULLAGE TESTS ARE ON A PASS/FAIL BASIS ONLY. <br /> TANK #1: REG UNLEADED TYPE: STEEL RATE: .019620 G.P.H. LOSS <br /> ULLAGE: PASS SIGNAL/NOISE: .05 <br /> TANK IS TIGHT. <br /> TANK #2: DIESEL FUEL 2 TYPE: STEEL RATE: .014914 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: .01 <br /> TANK IS TIGHT. <br /> EQUIPMENT: USTEST _- <br /> OTTL# 97-1143 <br /> OPERATOR: LYLE D. ,NIMMO SIGNATURE: <br />