Laserfiche WebLink
CONFIDENCE UST SERVICES,INC.' <br /> 417 Montclair Street <br /> Bak 'Leld. CA 93309 <br /> 800-339-9930 \ 805-631-3870 <br /> ALERT 1000 UND RFI ALERT 1050 TYr.T.AGR gVgTRM <br /> Precision Underground Storage Tank System Leak Test <br /> T T R .4R TR <br /> Test Date: 08/06/97 <br /> BILLING:CONFIDENCE UST SER. SITE:JIFFY LUBE <br /> 417 MONTCLAIR ST. 1130 N. MAIN STREET <br /> BAKERSFIELD, CA.93309 MANTECA, CA <br /> PRODUCT VOLUME %FULL WETTED NON-WETTED PRODUCT LEAK WATER IN <br /> (GAL) PORTION PORTION LTNF. DETECTOR TANK <br /> WASTE OIL 1000 65% -0.031 PASS-REMOTE FILL INCLUDE 0'. <br /> WATER BALANCE <br /> Measurements showed that water in the backfill area at the time <br /> of testing was below tank bottom, and therefore not a factor in test <br /> determination. A monitoring well or a well point was driven in the <br /> backfill area to determine that there is no water in the backfill at <br /> tank bottom. <br /> A precision test was performed on tanks at the above location using the <br /> Alert 1000 underfill system and the Alert 10SOX ullage system. I have <br /> reviewed the data produced in conjunction with this test for purpose of <br /> verifying the results and certifying the tank systems. The testing was <br /> performed in acorrdance with Alert protocol, and therefore satisfies <br /> all requirements for such testing as set forth by NFPA 329-92 <br /> and USEPA 40 CFR part 280. <br /> The results of testing are shown on the following page, and indicate <br /> whether the wetted and non-wetted portion passed or failed. Included <br /> with the report are reproduction of data compiled during the test which <br /> formed the basis for these conclusion. This information is stored in a <br /> permanent file if future verification of test results is needed. <br /> AL\NC 040 <br /> Test Certified By: <br /> ames J. Rich <br /> State cert#99-1072 <br />