Laserfiche WebLink
PUBLIC HEALTH SERVICES <br /> SAN JOAQUIN COUNTY <br /> ENVIRONMENTAL HEALTH DIVISION i < <br /> Karen Furst, M.D., M.P.H., Health Officer <br /> 304 East Weber Avenue, Third Floor • Stockton, CA 95202 <br /> 209/468-3420 <br /> October 6, 1998 <br /> To: Tex Stokley <br /> Stokley Construction <br /> P O Box 1008 <br /> Tracy CA 95378 <br /> From: Letitia Briggs—Sr. R.E.H.S. i3 <br /> San Joaquin Public Health Services <br /> Environmental Health Division <br /> 304 E. Weber Ave., 3" Floor <br /> Stockton CA 95202 <br /> RE: Incomplete Underground Storage Tank (UST) Installation Plan for 4075 E. <br /> Main Street, Stockton, CA <br /> The installation plan you submitted requires the following information prior to permit <br /> approval. <br /> 1. Applicants signature on permit application <br /> 2. Equipment and material specification sheets <br /> 3. The monitoring system must be listed in LG (Letter of Guidance) 113-12 <br /> 4. A Monitoring and Response Plan must be submitted for new installations prior to <br /> the opening of the station <br /> 5. The installation plans should include cross section of tank, secondary containment <br /> and 1(e) submittal of piping run and cross section plans <br /> 6. You must include drawings of sumps for tank and sump monitoring <br /> 7. The piping needs compatable leak detectors <br /> 8. Will the tank arrive with a vacuum on intersticial space? <br /> A Division of San Joaquin County Health Care Services <br />