Laserfiche WebLink
4. Spill/Overfill Containment Boxes <br /> Test Method Developed By: ❑Tank ManufacturerX❑ Industry Standard ❑Professional Engineer <br /> Test Method Used: ❑Pressure ❑vacuum ❑X Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:±0.002 <br /> Spill Box# 87 Spill Box# 91 Spill Box# Spill Box# <br /> ucket Diameter: 11" 11" <br /> Bucket Depth: 14" 14" <br /> Wait time: 15 min 15 min 15 min 15 min <br /> Test Start Time: 11:56 11:56 <br /> Initial Reading: 0.6909 5.4548 <br /> Test End Time: 12:11 12:11 <br /> Final Reading: 0.6900 5.4542 <br /> Test Duration(hh:mm): 00:15 00:15 00:00 00:00 <br /> Change in Reading: -0.0009 -0.0006 0.0000 0.0000 <br /> Pass/Fail Threshold or Criteria: ±0.002 ±0.002 ±0.002 ±0.002 <br /> Test Result: * Pass 0 Fail Pass Q Fail <br /> � Pass Fail - 0 Pass. *Fail <br /> Comments: <br /> 2 of 2 <br />