Date: 7-14-88 <br /> File Narne: GASPLAN5 <br /> THE CUSTOMER COMPANY <br /> EMERGENCY AND MONITORING PROCEDURES FOR GASOLINE STATIONS <br /> PLAN 5 <br /> MONITORING EQUIPMENT <br /> The store monitoring equipment consists of: <br /> a) Leak detectors in the product pipeline <br /> b) A Leak-X or Leak Sensor II alarm in backroom of store <br /> c) A visual inspection of the gas dispensers <br /> d) Underground trench liner for all product lines <br /> INSTRUCTIONS FOR STORE PERSONNEL <br /> a) LEAK DETECTORS - This is a device that is underground in the <br /> fi_rel system piping. There is one device per product. <br /> This device is designed to cut the fuel flow down to a trickle <br /> when it senses a leak or• pressure drop in the product line. <br /> There are several reasons for this device to trip: <br /> 1. A customer can hold the nozzle open before turning on the <br /> Pump, thus tripping it. <br /> 2. In c,�ld weather, the product car, contract while the station <br /> is closed at night. <br /> 3. The device could be defective. <br /> 4. The device is sensing a leak. <br /> WHAT TO DO <br /> If the leak detector trips, you can reset it by simply turning on <br /> one of the gas dispensers of that product type and letting it run <br /> for a minimum of 30 seconds without dispensing fuel from that <br /> nozzle or any other• of that product type. This pressurizes the <br /> line and resets the detector. <br /> If the leak detector continues to trip or starts to trip every <br /> morning, CALL THE MAINTENANCE DEPARTMENT 800-328-9966 <br /> If you cannot get the detector to reset or it trips more than <br /> once, then call the Maintenance Department and shut the product <br /> down that is giving the problem. <br /> NOTE : You do rot have to shut the whole gas island down, gust the <br /> product type that is giving you trouble. <br /> b) LEAK-X OR LEAK SENSOR II - In the backroom of the store is a <br /> 2 <br />