Laserfiche WebLink
f <br />IN1GRITY TANK TESTING <br />P. O. BOX 691736, STOCKTON, <br />March 17, 1993 <br />Mr. John Bourdon <br />McHenry Station and MiniMart <br />1405 Main Street <br />Escalon, Ca. 95320 <br />Dear Mr. Bourdon', <br />S VICES <br />CA. 95269 HEALTH <br />�" ALL 2'4 P,•f 2. 11 <br />Following is a summary of the precision testing we recently conducted on your <br />underground storage tank at the above site. <br />Enclosed are copies of the test worksheet, graphs, and/or computer generated <br />summations for your submittal to the appropriate governmental agency. <br />A tank system may be considered tight, according to the current regulations if the test <br />results shown below do not exceed 0.05 gph. If the results are beyond this parameter, <br />an unauthorized release may have occurred, and you should consider taking remedial <br />action. <br />TANK # OR <br />TANK <br />PRODUCT <br />TEST <br />WITHIN TIGHT <br />LOCATION <br />CAPACITY <br />CONTAINED <br />RESULTS <br />PARAMETERS <br />East <br />5,155 <br />U/L Prem Gaso <br />-.028 <br />Yes <br />Center <br />10,200 <br />U/L Reg Gaso <br />-.025 <br />Yes <br />West <br />6,260 <br />Diesel Fuel <br />-.009 <br />Yes <br />Please advise if you need additional information or service. <br />Sincerely, <br />&a Saw -rte <br />W. N. Savage <br />Certified Tester <br />STOCKTON (209) 474-1375 TOLL FREE (800) 262-8378 <br />