McHENRY STA & MINIMART <br />1405 MAIN ESCALON <br />JOHN BOURDON 838-7521 <br />TANK TESTER VER 2.01 <br />FUEL TYPE: U/L PREM EAST TNK <br />CAPACITY TANK 2: 5181 GALLONS <br />TEMPERATURE COEFFICIENT: 672 ppm/deg F <br />TEST CRITERIA: +0.000 GPH TO +0.000 GPH <br />03/17/92 TEST TIME FROM 13:38 TO 14:45 <br />DATA ANALYSIS INDICATES: <br />A GROSS VOLUME CHANGE OF: -0.022 GALLONS <br />A VOLUME CHANGE DUE TO TEMPERATURE OF: +0.009 GALLONS <br />A LIQUID VOLUME RATE OF CHANGE OF: <br />WITH A 99 % CONFIDENCE INTERVAL OF: <br />TESTER. !.100 <br />CUSTOMER .............. <br />--0.028 GPH <br />+/-0.001 GPH <br />(-0.027 TO -0.030 GPH) <br />