Laserfiche WebLink
Test Site: PENSKE TRUCK Lb NG <br /> ULLAGE TESTING DATA <br /> Test Method Used: UTS4T <br /> Test Date: 11-03-95 11-03-95 <br /> Talc Number: T 1 East T 2 West <br /> Product: Diesel Unlead <br /> True Capacity (gallons): 20149 12032 <br /> Ullage volume (gallons): 1427 4073 <br /> Fluid pressure on tank bottom (psi): 3.43 1.6 <br /> Ullage test pressure tpsi): 1.0 2.4 <br /> Stabilization time (minutes): 10 20 <br /> Fill start time: 2210 2100 <br /> Time to 1 psi: 2215 2105 <br /> Time to test pressure: 2216 2110 <br /> Start time - test 1: 2230 2130 <br /> Nitrogen flow (cfh): 0.20 0.20 <br /> Ullage Temperature ('F): 72.7 72.8 <br /> Finish time - test 1: 2245 2145 <br /> Final Nitrogen flow (cfh): 0.20 0.22 <br /> Start time - test 2: 2245 2200 <br /> Nitrogen flow (cfh): 0.20 0.20 <br /> Ullage Temperature ('F): 72.7 72.8 <br /> Finish time - test 2: 2300 2215 <br /> Final Nitrogen flow (cfhl: 0.15 0.20 <br /> Start time - test 3: <br /> Nitrogen flow (cfh): <br /> Ullage Temperature ('F): <br /> Finish time - test 3: <br /> Final Nitrogen flow (cfh): <br /> Pass/Fail PASS PASS <br /> Ullage Test Comments: None. <br /> NOTE: (2 CONSECUTIVE TESTS @ < 0.275 constitute a PASS) 13 CONSECUTIVE TESTS @ > 0.275 CONSTITUTE A fail) <br /> ProTant, kt - 3545 Lomita Boulevard, Suite G -Torrence, CA 90505 (310) 891-0470 <br />