Laserfiche WebLink
Test Date: 03/03/2005 - <br /> 10 Pw k �",,`A' Work Order: 2234954 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Type Tank or Disp Manufacturer Model or Diam./Width/Length Depth Test Method Start Initial Level Finish Fine Til Pass/ <br /> # Material ") C Time Level Change me Result Fail <br /> STP Sump 1 REG Western Fiberglass Fiberglass 36 84 Hydrostatic-Electronic 1255 15 .000 1325 .012 Pass <br /> STP Sump 2 PLS Western Fiberglass Fiberglass 36 84 Hydrostatic-Electronic 1257 15 .000 1327 .000 Pass <br /> STP Sump 3 PRM Western Fiberglass Fiberglass 36 84 Hydrostatic-Electronic 1357 15 .000 1427 .007 Pass <br /> STP Sump 3 DSL Western Fiberglass Fiberglass 36 84 Hydrostatic-Electronic 1355 15 .000 1425 .000 Pass <br /> Dispenser Pan 1/2 Western Fiberglass Fiberglass 36 24 Hydrostatic-Electronic 1538 10 .000 1553 .000 Pass <br /> Dispenser Pan 3 Western Fiberglass Fiberglass 24 24 Hydrostatic-Electronic 1553 10 .000 1608 .000 Pass <br /> Dispenser Pan 4/5 Western Fiberglass Fiberglass 36 24 Hydrostatic-Electronic 1535 10 .000 1550 .001 Pass . <br /> Dispenser Pan 6 Western Fiberglass Fiberglass 24 24 Hydrostatic-Electronic 1655 10 .000 1610 .000 Pass <br /> Dispenser Pan 7/8 Western Fiberglass Fiberglass 36 24 Hydrostatic-Electronic 1654 10 .000 1709 .000 Pass <br /> Dispenser Pan 9 Western Fiberglass Fiberglass 24 24 Hydrostatic-Electronic 1648 10 .000 1703 .000 Pass <br /> • <br /> Comments: <br />