Laserfiche WebLink
10/04/2004 02: 58 20936513 TANKNOLOGV • PAGE 03 <br /> INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> Mir Tankmijow <br /> TEST DATE:09/29/04 8900 SHOAL CREEK, BUILDING 200 WORK ORDER NUMBER2232464 <br /> CLIENT:USA PETROLEUM AUSTIN,TEXAS 78757(512)451.6334 SITE:us& N65 <br /> Tank ID: 12K 1 Tank manifolded: tr0 Bottom to top fill in inches: <br /> Product: UNLEADED Vent manifoided: NO Bottom to grade in inches: <br /> Capacity in gallons: 12,032 Vapor recovery manifolded: YSS FIII pipe length in inches: <br /> Diameter in inches: 96,00 Overfill protection: YES. FIII pipe diameter in inches: 4.0 <br /> Length in inches: 389 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: Dir STEEL Installed: ATG Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> start(in) End(in)Dipped Water Level: Start <br /> Falled/replaced Naw/passed Failedlreplaced <br /> Dipped Product Level: L.D.#1 L.D.fH L.D.fit L.D.02 <br /> Probe Water Level: Make: EEo JACKET Rtro JACKET <br /> Ingress Detected: Water Bubble Ullage Model: exly rx1V f <br /> Test time: S/N; 30501 6296 533%97 3257 <br /> IOpen time in sec: 5.00 <br /> Inclinometer reading: <br /> Holding psi: 14 <br /> VacuTect Test Type: NOT Resiliency cc: 150 NOT <br /> Vacu?ect Probe Entry Point: TESTED <br /> Test leak rate ml/m: 1e9.0 TEeTED <br /> Pressure Set Point: Metering psi: 9 <br /> Tank water level in Inches: Calib.leak in gph: 3.00 3.00 <br /> Water table depth in inches: Results: PASS FAIL <br /> Determined by(method): <br /> Result: COMMENTS <br /> COMMENTS <br /> Material: ENVIRON <br /> Diameter(in): 1.5 <br /> Length(ft): 120.0 <br /> Test psi: 5o <br /> Bleedback cc: 260 <br /> Test time(min): 60 NOT NOT NOT <br /> Start time: 11:28 TESTED TESTED TESTED <br /> End time: 12:28 <br /> Final gph: 0.000 <br /> Result: PASS <br /> Pump type: PRES8UR8 <br /> Pump make: RFD JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> Draft 10/04/2004 1419 MSHAW <br />