r 1 <br /> SHIRLID ENVIRONMENTAL TESTINq$_.L.C. <br /> P.O. Box 219 1928 Tyler Avenue, Suite K <br /> Nebraska City, NE 68410 South EI Monte, CA 91733 <br /> 402-873-4077/800-447-3490 626-444-7447/800-533-4030 <br /> Secondary Containment Test Report <br /> Tank and Piping Annular <br /> SITE: DATE: 12-7-2001 <br /> USA Petroleum #065 CONTACT: <br /> 2500 West Lodi PHONE: 209-333-9834 <br /> Lodi CA 95242 JOB #: T5 007073 <br /> Tank Annular Space Vacuum Test <br /> Tank# - 1 2 3 4 <br /> Product Unleaded Unleaded Plus Premium Diesel <br /> Type ofTank(SDW/FRP) <br /> D <br /> FRP, DW/FRP) DW Steel DW Steel DW Steel DW Steel <br /> Start Time 1500 1200 1244 1244 <br /> End Time 1530 1230 1314 1314 <br /> Starting Vacuum 11 11 11 11 <br /> Ending Vacuum 10.9 11 11 11 <br /> Change in Vacuum .1 0 0 0 <br /> Results Pass Pass Pass Pass <br /> Line Annular Space Pressure Test <br /> =Time <br /> umbe 1 2 3 4 <br /> Unleaded Unleaded Plus Premium Diesel <br /> DW Enviroflex DW Enviroflex DW Enviroflex DW Enviroflex <br /> RP) <br /> 955 1036 1113 <br /> End Time 1025 1106 1143 <br /> Starting Pressure 3 3 3 <br /> Ending Pressure 2,9 2.8 3 <br /> Change in Pressure .1 .2 0 <br /> Results Not Tested Pass Pass Pass <br /> 989 Test Type <br /> Technician: James S. Davis ® Incon TS-STS ®Vacuum <br /> Tester ID# 97-1579 ❑ Caldwell ® Pressure <br /> ❑ Fibre-Lite <br />