Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> '-i 723nkno/ogy <br /> TEST DATE:12/02/03 8900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER2229244 <br /> CLIENT:VALERO AUSTIN,TEXAS 78757(512)451-6334 SITE:ULTRAMAR 492 <br /> TANK INFORMATION <br /> Tank ID: 87 1 Tank manifolded: NO Bottom to top fill in inches: 134.0 <br /> Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: 141.0 <br /> Capacity in gallons: 14,130 Vapor recovery manifolded: YES Fill pipe length in inches: 38.0 <br /> Diameter in inches: 95.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 337 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW STEEL Installed: ATG Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> TANK TEST RESULTS Test Method:VacuTect LEAK DETECTOR TEST RESULTS Test method: LT-1 <br /> Start(in) End(in) <br /> Dipped Water Level: New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Product Level: <br /> L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Probe Water Level: Make: RED JACKET <br /> Ingress Detected: Water Bubble Ullage Model: Px1v <br /> Test time: S/N: 30601-8516 <br /> Inclinometer reading: Open time in sec: 3.00 <br /> Holding psi: 14 <br /> VacuTect Test Type: NOT Resiliency cc: 90 NOT <br /> VacuTect Probe Entry Point: TESTED <br /> Test leak rate ml/m: 189.0 TESTED <br /> Pressure Set Paint: Metering psi: 14 <br /> Tank water level in inches: Calib. leak in gph: 3.00 <br /> Water table depth in inches: Results: BASS <br /> Determined by(method): <br /> Result: <br /> COMMENTS <br /> COMMENTS <br /> LINE TEST RESULTS Test type: TLD-1 <br /> LINE A B C D <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length (ft): 40.0 <br /> Test psi: 50 <br /> Bleedback cc: 0 <br /> Test time(min): 40 NOT NOT NOT <br /> Start time: 08:50 TESTED TESTED TESTED <br /> End time: 09:30 <br /> Final gph: -0.014 <br /> Result: BASS <br /> Pump type: PRESSURE <br /> Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 12/09/2003 08:17 <br />