Laserfiche WebLink
. • Page_of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Uses: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Measuring Equipment Used for Testing: Liquid Filled Vac Gauges <br /> Tank#1 RU Tank#2 SU Tank 43 <br /> Tank Capacity: 14130 14130 <br /> P ry� <br /> Tank Material: Fibersteel Fibersteel <br /> Tank Manufacturer: Trusco Trusco <br /> Product Stored: RU SU <br /> Wait time between applying IOMIN <br /> pressure/vacuum/water and starting IOMIN <br /> test: <br /> Test Start Time: 0730 0745 <br /> Initial Reading( JR : -10"HG -10"HG <br /> Test End Time: 0830 0845 <br /> Final Reading(RF): -10"HG -10"HG <br /> Test Duration: 1 HR IHR <br /> Change in Reading(RF-R,): 0 0 <br /> Pass/Fail Threshold: 2" 2 <br /> Test Result: PASS PASS <br /> Was sensor removed for testing? YES YES <br /> Was sensor properly replaced after YES YES <br /> testing? <br /> Comments— <br /> December 2001 <br /> SWRCB <br />