Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> IP Tanknology <br /> TEST DATE:12/02/04 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER2233193 <br /> CLIENT:VALERO AUSTIN,TEXAS 78759(512)451-6334 SITE:ULTRAMAR 492 <br /> TANK INFORMATION" -- <br /> Tank ID: 87 1 Tank manifolded: NO Bottom to top fill in inches: 134.0 <br /> Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: 141.0 <br /> Capacity in gallons: 14,130 Vapor recovery manifolded: YES Fill pipe length in inches: 38.0 <br /> Diameter in inches: 96.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 337 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW STEEL Installed: Axa Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> TANK TEST RESULTS Test Method:VacuTect LEAK DETECTOR TEST RESULTS -Test method: FTA <br /> Dipped Water Level: Start(in) End(in) New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Product Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Probe Water Level: Make: RED JAcrET <br /> Ingress Detected: Water Bubble Ullage Model: FXIV <br /> Test time: S/N: 30601 8516 <br /> IOpen time in sec: 3.00 <br /> Inclinometer reading: <br /> Holding psi: 14 <br /> VacuTect Test Type: NOT Resiliency cc: 75 NOT <br /> VacuTect Probe Entry Point: TESTED Test leak rate ml/m: 189.0 TESTED <br /> Pressure Set Point: Metering psi: 13 <br /> Tank water level in inches: Calib. leak in gph: 3.00 <br /> Water table depth in inches: Results: PASS <br /> Determined by(method): <br /> Result: <br /> COMMENTS <br /> COMMENTS <br /> LINE TEST RESULTS Test type: TLD-1- <br /> LINE. A B C D <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length(ft): 70.0 <br /> Test psi: So <br /> Bleedback cc: 85 <br /> Test time(min): 30 NOT NOT NOT <br /> Start time: 12:25 TESTED TESTED TESTED <br /> End time: 12:55 <br /> Final gph: 0.006 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 12/08/2004 07:56 <br />