Laserfiche WebLink
LDT 5000 Field Test Apparatus X4111}Y'ay1'p j�' <br /> 44 Tanknology Line Leak Detector Test �Pagr!�R1' .• - <br /> Work Order: 2327782 Date: 5/4/2016 <br /> Site Name/ID: DP&DK INV. INC./DP&DK <br /> Address: MARCH LANE SHELL 1206 E. MARCH LANE <br /> City: STOCKTON State: CA Zip: 95210 <br /> Tank ID 1 2 3 <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 9 9 9 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-200C Vaporless LD-200 <br /> Serial No. 07061368 01110513 12121061 <br /> Pump Operating Pressure(psi) 28.00 30.00 27.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 26.00 29.00 27.00 <br /> N/A for Electronic LD's <br /> Resiliency(ml) 180.00 210.00 120.00 <br /> N/A for Electronic LD's <br /> Metering PSI 15 10 15 <br /> N/A for Electronic LD's <br /> Opening Time(sec) 12 5 9 <br /> N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Todd Inderbitzen Certification#: 115137 <br /> Technician Signature: <br /> — Expire Date: 9/30/2018 <br /> Environmental Compliance for Petroleum Systems <br /> ©2016 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />