0 * <br /> RECEIVED <br /> SWRCB,January 2002 Page 1 of 1 <br /> 9. SPELL/OVERFILL CONTAINMENT BOXES MAY 15 2 Q 1.4 <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br /> ENVIRONMENTAt <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: Spill Bucket Manufacturer Fv1J Industry Standard ❑ Professional Engineer <br /> F Other(Specify): <br /> Test Method Used By: r Pressure ❑ Vacuum 0 Hydrostatic <br /> F Other(Specify): <br /> Test Equipment Used: LAKE TEST Equipment Resolution:0.0625 in. <br /> Spill Box#Tank 1 Spill Box#Tank 2 Spill Box#Tank 3 <br /> REGULAR-Fill I - PREMIUM-Fill 1- Diesel-Fill 1 -Direct- Spill Box# <br /> Direct-Grade level Direct-Grade level Grade level <br /> Bucket Diameter: 12.00 12.00 12.00 <br /> Bucket Depth: 12.00 12.00 12.00 <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min 5 min min <br /> starting test <br /> Test Start Time: 09:00:00 09:00:00 09:00:00 <br /> Initial Reading(Rj): 11.50 in.H2O 12.00 in.H2O 12.00 in.H2O <br /> Test End Time: 10:00:00 10:00:00 10:00:00 <br /> Final Reading(RF): 11.50 in.H2O 12.00 in.H2O 12.00 in.H2O <br /> Test Duration: 1 hr 1 hr 1 hr <br /> (RF-RO: 0.00 in.H2O 0.00 in.H2O 0.00 in.H2O <br /> Pass/Fail Threshold or Criteria: +/-0.00 +/-0.00 +/-0.00 +/- <br /> Test Result: Pass Pass Pass <br /> Comments-(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2317840 <br />