Laserfiche WebLink
wool* <br /> RECEIVED <br /> NOV 2 / 2013 <br /> ENVIRONMENTAL <br /> HEALTH DEPARTMENT <br /> Quality Petroleum Equipment <br /> LDT - 890 Test Form <br /> Test Information <br /> Date: 111/18/2013 Test Company: Mid Valley Consulting & General Eng. <br /> Telephone: 530-749-9892 Contact: James Day <br /> Site ID: March & Bianchi Chevron Address: 1916 March Lane_ <br /> City: Stockton State: Ca <br /> Type of Test Equipment: VMI LDT- 8901AF <br /> Submersible Pump Identification <br /> MFG: Red Jacket Model No: R20001-3R-J1 Serial No: 065818A <br /> Leak Detector Identification <br /> MFG: Veeder Root Model No: MID Serial No: 273641 <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1. Type of Pipe, FRP 2. Diameter of Pipe: 2 3. Length of Pipe 140' <br /> 4. Burial Depth of Leak Detector: 34" 5. Kind of Fuel: Diesel _ 6. Date of Last Test: 2012 <br /> Test Conditions <br /> 1. Operating Pump Pressure: 41 PSI 2. Gallon per hour test rate:_3@10 @10 psi <br /> 3. Static Line Pressure (Pump Off): 22 PSI 4. Bleed back Test (Pump Off): 110 ml <br /> S. Step-Through time to full flow 3 seconds (0 psi to full pump pressure, no leak) <br /> S. Leak detector stays in Leak Search Position with a 3 GPM leak-Yes: X PASS No: FAIL <br /> 7. Was the leak detector adjusted - Yes:_ No: _X <br /> Symptoms <br /> 1. Won't find 3 GPM leak: 2. Stays in Slow Flow: <br /> 3. Other- <br />