Laserfiche WebLink
RECEIVED <br /> JAN 0 2 2015 <br /> ENVIRONMENTAL, <br /> Ifcpr.J'�C7�Or.mV1T <br /> Quality Petroleum Equipment <br /> LDT - 890 Test Form <br /> Test Information <br /> Date: 11/18/2014 Test Company: Mid Valley Consulting & General Eng. <br /> Telephone: 530-749-9892 Contact: James Day <br /> Site ID: March & Bianchi Chevron Address: 1916 March Lane <br /> City: Stockton State: Ca <br /> Type of Test Equipment: VMI LDT- 8901AF <br /> Submersible Pump Identification <br /> MFG: Red Jacket Model No: R20001-3R41 Serial No: 065817R <br /> Leak Detector Identification <br /> MFG: Veeder Root Model No: PIID Serial No: 274820 <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1. Type of Pipe:FRP 2. Diameter of Pipe: 2 3. Length of Pipe 25W <br /> 4. Burial Depth of Leak Detector: 32" 5. Kind of Fuel: 91 6. Date of Last Test: 2013 <br /> Test Conditions <br /> 1. Operating Pump Pressure: 27 PSI 2. Gallon per hour test rate: 3 @10 psi <br /> 3. Static Line Pressure (Pump Off). 13 PSI 4. Bleed back Test (Pump Off): ml <br /> 5. Step-Through time to full flow 6 seconds (0 psi to full pump pressure, no leak) <br /> 6. Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: X PASS No: FAIL <br /> 7. Was the leak detector adjusted - Yes: No: _ X -. <br /> Symptoms <br /> 1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br /> 3. Other: <br />