Laserfiche WebLink
RECEIVED <br /> JAN 0 2 2015 <br /> ENVIRONMENTAL <br /> ���a'.Tu 7FPQPT�fC�T <br /> Quality Petroleum Equipment <br /> LOT - 890 Test Form <br /> Test Information <br /> Date: 11/18/2014 Test Company- Mid Valley Consulting & General Ena. <br /> Telephone: 530-749-9892 Contact: James Dav <br /> Site ID: March & Bianchi Chevron Address: 1916 March Lane <br /> City: Stockton State: Ca <br /> Type of Test Equipment: VMI LDT-8901AF <br /> Submersible Pump Identification <br /> MFG: Red Jacket Model No: R20001-3R-J7 Serial No: 873901H <br /> Leak Detector Identification <br /> MFG: Veeder Root Model No: Elld Serial No: 27364C <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1. Type of Pipe:FRP 2. Diameter of Pipe: 2 3. Length of Pipe 240' <br /> 4. Burial Depth of Leak Detector: 33" 5. Kind of Fuel: 87 6. Date of Last Test: 2013 <br /> Test Conditions <br /> 1. Operating Pump Pressure: 27 PSI 2. Gallon per hour test rate:___ 3 @10 psi <br /> 3. Static Line Pressure (Pump Off), 15 PSI 4. Bleed back Test (Pump Off): ml <br /> 5. Step-Through time to full flow 7 seconds (0 psi to full pump pressure, no leak) <br /> 6. Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: X PASS <br /> No: FAIL <br /> 7. Was the leak detector adjusted - Yes: No: _X_ <br /> Symptoms <br /> 1. Won't find 3 GPH leak:_______ _ 2. Stays in Slow Flow: <br /> 3. Other: <br />