Laserfiche WebLink
ITTSIntegrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> November 21 , 1988 <br /> Randall F . Thomas <br /> Port of Stockton Foods <br /> P . 0 . Box 30 Site : 1950 East Miner <br /> Stockton, California 95201 Stockton, California <br /> Dear Mr . Thomas : <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate governmental <br /> agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the loss or gain is less than . 05 gallons per one hour <br /> of testing . If the results are beyond these parameters , you <br /> snould consider taking some remedial action . <br /> TANK N/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY C014TAI14ED RESULTS TANK PARAMETERS <br /> North 2 , 000 Diesel - . 013 Yes <br /> Please contact us if you need additional assistance or <br /> information . <br /> Sincerely, <br /> W,�sr✓dC�z� <br /> W. Savage <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />