ITTSIntegrity Tank Testing Systems, Inc. <br /> \ EST DATA AND <br /> N�cJ TEST RESULT'S <br /> v\ <br /> F�\IFEC �\��✓~ 11/ 19/87 <br /> Mr. Lee Gunn <br /> _ . Port of Stockton Foods _ <br /> P. 0. Box 30 <br /> Stockton, California 95201 <br /> Dear Mr. Gunn, <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than .02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action . <br /> TANK O/- TANK PRODUCT TEST WITHIN TiGNT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> 1950 E. Miner 2 ,000 Diesel Fuel -. 016 Yes <br /> Please contact us if you need additional assistance or <br /> information, <br /> Sincerely, <br /> w.b.'400%2- <br /> W. N. Savage <br /> Certified Tester <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />