Laserfiche WebLink
E March 24 , 1987 <br /> VCircle K Corporation <br /> 5811 Manzanita Avenue <br /> R Carmichael , California 95608 <br /> P Attn : Pat Wright <br /> N ° <br /> M g RE: Petro-Tate Tank Test <br /> E 0 <br /> N X Dear Pat : <br /> T 2 On March 19 , 1987 , we performed a Petro-Tite Tank Test <br /> l4 0 at Store # 1334- 2650 Mt. Diablo Street , Stockton, California . <br /> L g The test was performed by Don Troxell , E .P .E. Technician . <br /> The NFPA code 329.02 criteria for a tight tank system is a <br /> S tolerance of . 050 gallons per hour . Because of the almost <br /> P infinite variables involved , this is not intended to be a <br /> T <br /> E Tmathematical tolerance and is not the permission of <br /> T K actual leakage . <br /> R T PRECISION TANK TEST <br /> N <br /> L Tank 2 - Middle <br /> E C Size - 10 ,000 gallons <br /> V A Product - Premium Unleaded <br /> The test showed a positive . 011 gallons per <br /> M 5 hour . Based on the above criteria , we find <br /> 2 the tank system tested mathematically tight . <br /> 0 <br /> E 1 This concludes our test and findings on March 19 , 1987 . <br /> N ^ IIf you have any questions regarding the results , please <br /> 2 contact me . An extra copy has been included for you to <br /> 0notify your local County Health Department , Environmental <br /> 0 <br /> Health . If you have any questions on what your next step <br /> N v should be, please contact your local Health Department <br /> E 4 immediately . <br /> E 3 <br /> S ' erely , <br /> I o <br /> N 2 <br /> G 2 Don Troxe <br /> Certified Tank Testing Technician <br /> DT/bm <br /> N Encl . <br /> C <br />