Vac System Testing <br /> This section describes a sequence of procedures and tests necessary to complete the Vac Sensor installation: <br /> 1. ATM Pressure Sensor setup <br /> 2. Vac Sensor setup <br /> 3. Vacuum integrity test prior to filling tank* <br /> 4. Manual test* <br /> 5. Operability test <br /> *NOTE:Only one of these two tests is required to complete the installation. <br /> ATM Pressure Sensor Setup <br /> The ATM Pressure Sensor is factory installed in the SmartSensor/Press module and preassigned to channel B.At <br /> least one SmartSensor/Press module,which contains the ATM Pressure Sensor,must be installed in the console. <br /> You must configure at least one ATM Pressure Sensor for use by the Vac Sensor System or a Setup Data Warning <br /> will occur. NOTE: if more than one SmartSensor/Press module is installed,only one ATM Pressure Sensor needs <br /> to be configured. <br /> Look in console and note the slot position of the SmartSensor/Press module. Enter the Setup Mode and press <br /> the FUNCTION key until you see the message: <br /> SMARTSENSOR SETUP <br /> PRESS<STEP>TO CONTINUE <br /> Press STEP until you see the message: <br /> SS CONFIG-MODULE n <br /> SLOTx-XXXXXXXX <br /> Where x is the slot number containing the SmartSensor/ Press module. Press the key to move the cursor to the <br /> last(8th) X. Press CHANGE and the message below should appear: <br /> SLOTx-XXXXXXX8 <br /> PRESS<STEP>TO CONTINUE <br /> Press STEP: <br /> ENTER SMARTSENSOR LABEL <br /> s 8: <br /> NOTE:In the example above,the ATM P sensor position is 8 but it could bel 6,32,or 40 depending on the <br /> SmartSensor's module number. <br /> Press CHANGE and enter a label: <br /> ENTER SMARTSENSOR LABEL <br /> s 8:(ATMP Sensor Label) <br /> 19 <br />