Laserfiche WebLink
Emergency • <br /> Emergency Shutoff Valve O <br /> UL listed...required on underground tank motor fueling systems. UL <br /> The emergency shutoff valve,or"impact valve",is installed on <br /> the fuel line directly under the dispenser.It is intended to shut off <br /> the flow of product in the event of impact and/or fire involving <br /> the dispenser. <br /> In normal operation,the valve is left open,held in position by a <br /> fusible link.A shear section is located in the upper half of the valve <br /> and should be installed level with the base of the dispenser.In an Fig.636U Fig.636F <br /> emergency,the handle releases and the spring-loaded poppet <br /> assembly will close. <br /> Important Warning...this valve requires periodic inspection to <br /> ensure the shutoff mechanism is operating correctly.Always <br /> shutoff the power to the dispenser when changing filters or doing <br /> maintenance.This valve is not intended to be used as a"block Fig.636CM <br /> valve"and should not be opened under pressure.Opening under <br /> pressure can damage or distort internal components. Sizes available <br /> W x 1%" 636F Female connections...unibody <br /> Construction Details 11W x 111V 636M Male top connection...unibody <br /> Body and shear section...cast iron(epoxy coated) I W x 1%' 636U Union top connection...unibody <br /> Disc...Viton® 111rx 1'R' 636CF Female conmciions...containment <br /> O-rings...Vitons 1'h"x 1%" 636CM Male top connection...containment <br /> Gasket...graphite 1'h'x 1Y:" 636CU Union top connection...containment <br /> T x 1 h 636F Female connections...unibody <br /> Shaft...stainless steel Tic 111V 636M Male top connection...unibody <br /> Handle...aluminum 2"x 1%" 636U Union top wnnection...unibody <br /> Unibody incorporates U-bolt and post mount bracket connec- 2"x 1W 636CF Female connections...containment <br /> tions with male,female and union style pipe threads(NPT)at 2"x 1%d' 636CM Male top connection...containment <br /> the outlet(top connection). 2"x 1'1W 636CU Union top connection...containment <br /> 2"x 2" 636M Male top connection...unibody <br /> Also available with regular and containment style inlet.(Con- 2'x 2" 636CM Male top connection...containment <br /> tamment style is made for direct hookup to secondary contain- 2"x 2" 636F Female connections...unibody <br /> ment piping.) 2"x 2" 636CF Female connections...containment <br /> . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <br /> ® r e <br /> Vapor Recovery Fig.323SA <br /> Used for Stage I Vapor Recovery.Adaptors are installed <br /> on the VR riser of UST with coupling connection to fit <br /> vapor recovery hose on truck.Various styles available <br /> (listed below). •'�.: <br /> Fig 323...aluminum adaptor(threaded). i <br /> Fig.323B...aluminum adaptor(threaded)with brake <br /> interlock mounting pad.(Available without internals). Fig.323 Fig.3236 <br /> Fig.323C...aluminum cap,cam levers to fit VR adaptors. <br /> Lockable with Buna-N gasket and orange powder coat. <br /> Fig. 323SA...brass swivel adaptor. <br /> Fig. 323XB...brass adaptor(threaded). Fig. Size Weight <br /> Construction Details Fig.323 4"adaptor x 3"NPT 3.5 lbs <br /> Fig.323 4"adaptor x 4"NPSM 3.5 lbs <br /> Body...aluminum (hard-coated) Fig.3238 3"x 4" 4.0 lbs. <br /> Disc...Buna-N Fig.3238 4"adaptor x 4"NPSM 4.251bs <br /> Stem...plated brass Fig.323C 4"Cap 2.0 lbs <br /> Is <br /> Spring...stainless steel Fig.323SA 4'x 4" 10.75 Itis. <br /> Viton®available Fig.323XB 4"adaptor x 4"NPSM 12.25 lbs <br /> Code Compliance Fig. 323C <br /> CARB EVR Approved <br /> 4" Fig.323 and 4"323XB are CARB approved.4"Fig.323C is CARB EVR approved. <br /> Page 10 V Morrison Bros. Co. 800.553.4840 <br />