Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> J'P'rarArmlaw <br /> TEST DATE: 01/15/04 6900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER: 2229673 <br /> AUSTIN,TEXAS 78757(512)451-6334 <br /> CLIENT: V88DER ROOT - CMS SITE: SAFENAY INC.. 1769 <br /> Tank ID: lox 1 Tank manifolded: NO Bottom to top fill in inches: 178.0 <br /> Product: REGULAR Vent manifolded: YES Bottom to grade in inches: 188.0 <br /> Capacity in gallons: 20,073 Vapor recovery manifolded: YES Fill pipe length in inches: 58.0 <br /> Diameter in inches: 120.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 414 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: FRP CLD ST Installed: ATG Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced <br /> Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> UFT/OFT: Make: VEEDERROOT <br /> Fluid volume in gallons: Model: ELECTRONIC <br /> Tank water level in inches: SIN: <br /> Test time: NOT Open time in sec: <br /> Number of thermisters: TESTED Holding psi: 24 WOT <br /> Specific gravity: Resiliency cc: TESTED <br /> Water table depth in inches: Test leak rate ml/m: 189.0 189.0 <br /> Determined by(method): Metering psi: <br /> Leak rate in gph: Calib. leak in gph: 3.00 <br /> Result: Results: PASS <br /> COMMENTS COMMENTS <br /> Test time: Material: FLEX FLEX <br /> Ullage volume: Diameter(in): 1.5 1.5 <br /> Ullage pressure: Length (ft): 230.0 230.0 <br /> Results: Test psi: <br /> Bleedback cc: <br /> DATA FOR UTSAT ONLY: Test time (min): <br /> Test 1:Start time: <br /> Time Of test 1: Finish psi: NOT NOT NOT NOT <br /> Temperature: NOT Vol change cc: <br /> Test 2:Start time: TESTED TESTED TESTED TESTED <br /> Flow rate (cfh): TESTED Finish psi: <br /> Time of test 2: Vol change cc: <br /> Test 3:Start time: <br /> Temperature: Finish psi: <br /> Flow rate(cfh): Vol change cc: <br /> Time of test 3: Final gph: <br /> Temperature: Result: <br /> Flow rate(cfh): Pump type: PRESSURE PRESSURE <br /> COMMENTS Pump make: FE PETRO FE PETRO <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 01/22/2004 08:34 SBOWERS <br />