Laserfiche WebLink
REOFIVED <br /> MAY 12 2017 <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br /> Quality Petroleum Equipment <br /> LDT - 890 Test Form <br /> Test Information <br /> Date: 4/24/2017 Test Company: Mid Valley Consulting & General Eng. <br /> Telephone: 530-749-9892 Contact: James Dav <br /> Site ID FAST AND EASY Address: 10878 N. HWY 99 <br /> City: STOCTON State: <br /> Type of Test Equipment: VMI LDT - 890\AF <br /> Submersible Pump Identification <br /> MFG: RED JACKET Model No: P150S1 Serial No: 1726 <br /> Leak Detector Identification <br /> MFG: VMI Model No: LD 2000 Serial No: 1107 <br /> Replacement Leak Detector Identification <br /> MFG Model No: Serial No <br /> Line Conditions <br /> 1. Type of Pipe: FRP 2. Diameter of Pipe: 2" 3. Length of Pipe 110' <br /> 4. Burial Depth of Leak Detector: 22" S. Kind of Fuel: 91#1. 6. Date of Last Test: 2016 <br /> Test Conditions <br /> 1. Operating Pump Pressure: 28 PSI 2. Gallon per hour test rate: 3 _@10 psi <br /> 3. Static Line Pressure (Pump Off): 12 PSI 4. Bleed back Test (Pump Off): 140 ml <br /> 5. Step-Through time to full flow 3 seconds (0 psi to full pump pressure, no leak) <br /> 6. Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: X PASS No: FAIL <br /> 7. Was the leak detector adjusted - Yes: _ X No: <br /> Symptoms <br /> 1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br /> 3. Other: <br />