Laserfiche WebLink
S —T�tNK-TRK r:k"-TEK ENVIRONMENTAL CORPORAT101 RECEIVED <br /> APR 14 2014 <br /> ENVIRONMENTAL <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICAT16fi S ENT <br /> Date: 41112014 Work Order# 14040101-7 <br /> Location: SHANE 8 DAVE'S Contact: MIKE EL/ASON <br /> 3550 HWY 99 <br /> STOCKTON CA 95215 Telephone: (209)948-9412 <br /> SUMP# 1/2 1/2 <br /> DIESEU <br /> PRODUCT 87 RED DYE <br /> LD TYPE Mechanical, PLLD, (P)LLD I M M <br /> LD MANUFACTURER FE PETRO VMI <br /> LD MODEL MLD STP LD2000 <br /> LD SERIAL NUMBER 02121178 07051003 <br /> SUMP CONDITION DRY DRY <br /> RESILIENCY 150 ML 200 ML <br /> OPERATING PRESSURE 28 PSI 28 PSI <br /> OPENING TIME 3 SEC 3 SEC <br /> METERING PRESSURE 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 12 PSI 18 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? N/A N/A <br /> LD PASS OR FAIL? PASS PASS <br /> Comments: <br /> Technician: RICHARD THOMAS Contractor Lic. # 803705 <br /> Signature: <br /> PO BOX 5850,RIVERSIDE,CA 92517-5850 TEL 951-779-4999 FAX 951.788.7089 <br /> W W W,TANK-TEK.COM <br />