Laserfiche WebLink
r <br /> -T K <br /> PRESSURIZED PIPING LEAK DETECTION CERTIFICATION SHEET <br /> Date: 312112012 Work Order# 12032101-5 <br /> Location: SHANE&DAVES Contact: <br /> 3550 HWY 99 <br /> STOCKTON, CA 95215 Telephone: (209)948-9412 <br /> SUMP# <br /> PRODUCT 87 RED DIESEL <br /> LD TYPE Mechanical PLLD (P)LLD I M M <br /> LD MANUFACTURER VMI VMI <br /> LD MODEL LD 2000 LD 2000 <br /> LD SERIAL NUMBER UNREADABLE UNREADABLE <br /> SUMP CONDITION DRY DRY <br /> RESILIENCY 68 ML 55 ML <br /> OPERATING PRESSURE 28 PSI 26 PSI <br /> OPENING TIME 3 SEC 3 SEC <br /> METERING PRESSURE 10 PSI 10 PSI <br /> FUNCTIONAL ELEMENT HOLDING PRESSURE 14 PSI 14 PSI <br /> LEAK RATE LD DETECTED 3 GPH 3 GPH <br /> DOES LD DETECT 3 GPH LEAK RATE? YES YES <br /> DOES VEEDER-ROOT CONSOLE ALARM? NO NO <br /> LD PASS OR FAIL? PASS PASS <br /> Comments: <br /> Technician: MIKE LAWRENCE Contractor Lie. # 803705 <br /> Signature: <br /> TANK-TEK ENVIRONMENTAL CORPORATION <br /> 607 Elmira Road,PMB 336,Vacaville,CA 95687 — Ph.(707)446-6151 - Fax (707)446-6192 <br /> 31828 Carole Chamberlin,Temecula, CA 92591 — Ph.(951)699-8058 - Fax(951)699-8059 - E-mail:bballreich@verizon.net <br />