Laserfiche WebLink
I 11_VL.I v 16MLaw <br /> ~ a/ OCT 24 2013 <br /> SWRCB,January 2002 ENVIROW TRAVI <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES HEALTH DEF: :NT <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested r <br /> Test Method Developed By: r Spill Bucket ManufacturerC`. Industry Standard r Professional Engineer <br /> r Other(Specify): <br /> Test Method Used By: r Pressure r Vacuum r Hydrostatic <br /> r Other(Specify): <br /> 'fest Equipment Used:VACUUM TEST Equipment Resolution:0.1 gph <br /> Spill Box#Tank T-I Spill Box#Tank T-2 <br /> RUL-Fill 1 -Direct- PUL-Fill 1-Direct- Spill Box# Spill Box# <br /> Grade level Grade level <br /> Bucket Diameter: 14.00 14.00 <br /> Bucket Depth: 12.00 12.50 <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min min min <br /> starting test <br /> Test Start Time: 09:15:00 09:29:00 <br /> Initial Reading(RI): 30.00 in.H2O 12.50 in. <br /> Test End Time: 09:16:00 10:29:00 <br /> Final Reading(RF): 29.00 in.H2O 12.50 in. <br /> Test Duration: 1 min I hr <br /> Change in Reading(RF-RI): -1.00 in.H2O 0.00 in. <br /> Pass/Fail Threshold or Criteria: +/-4.00 +/-0.00 +/- +/- <br /> Test Result: Pass Pass <br /> Comments-(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2313415 <br />