Laserfiche WebLink
Page 1 of 1 <br /> TANK ANNULAR TESTING <br /> Test Method Developed By: P Tank Manufacturer 1 Industry Standard r Professional Engineer <br /> r Other(Specify) <br /> Test Method Used By: r Pressure FV Vacuum r Hydrostatic <br /> r Other(Specify) <br /> Test Equipment Used:gauge Equipment Resolution: .20" <br /> Tank# T-1 Tank# T-2 Tank# <br /> Is Tank Exempt From Testing?' ('Yes IT No r Yes(:No r Yes r No <br /> Tank Capacity'. 10028 10028 <br /> Tank Material: Steel Steel <br /> Tank Manufacturer: total containment total containment <br /> Product Stored: RUL PUL <br /> Wail time between applying 5 min 5 min min <br /> pressure/vacuum/water and starting test: <br /> Test Start Time: 09:10:00 091000 <br /> Initial Reading(RI): 15.00000 in. HG 15.00000 in. HG <br /> Test End Time: 08'.20'.00 08:20:00 <br /> Final Reading(RF): 9.00000 in. HG 14.00000 in. HG <br /> Test Duration: 23.1 hr 23.1 hr <br /> Change in Reading(RF-Ri): -8.00000 in. HG -1.00000 in. HG <br /> Pass/Fail Threshold or Criteria: +/-5,00000 +/-5 00000 +/- <br /> Test Result: Fail Pass <br /> Was sensor removed for testing? 0 Yes r Nor NA G. Yes r No r NA r Yes r No NA <br /> Was sensor properly replaced and verified IT Yes r No r NA IT Yes r Nor NA r Yes r Nor NA <br /> functional after testing? <br /> Comments?(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br /> both annular tests were started on 4-9-13 at 9:10 and ended 4-10-13 at 8:20. <br />