LD 5000 Field Test Apparatus Page 1 of 1 <br /> jfw Tanknology Line Leak Detector Test <br /> Work Order: 2319458 Date: 10/17/2014 <br /> Site Name/ID: 7-ELEVEN#17334 MKT 2368(N-747)/17334 <br /> Address: 4501 N PERSHING AVE @ ROSEMARIE LN <br /> City: STOCKTON State: CA Zip: 95207 <br /> ank lD T-1 T-2 <br /> Product RUL PUL <br /> Product Line 1 1 <br /> rested From 2 1 <br /> xisting/New Existing Existing <br /> echanical/Electronic Mechanical Mechanical <br /> anufacturer/Model Red Jacket FX1 Vaporless LD-200 <br /> erial No. 41200-1960 12091311 D—E-R.A.Rlh ENT <br /> Pump Operating Pressure(psi) 30.00 26.00 <br /> alibrated Leak(ml/min) 189.0 189.0 <br /> alibrated Leak(gph) 3.00 3.00 <br /> Holding PSI 30.00 20.00 <br /> NIA for Electronic Lo's <br /> Resiliency(ml) 165.00 90.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 10 15 <br /> NIA for Electronic Lo's <br /> pening Time(sec) 5 3 <br /> NIA for Electronic Lo's <br /> est Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Gilbert Garcia Certification#: 100037 <br /> Technician Signature: L Expire Date: 8/5/2016 <br /> Environmental Compliance for Petroleum Systems <br /> 02014Tank d,yInc.Austin TX. NInglxsreserved ranwolo .o <br />