Laserfiche WebLink
Imp <br /> SWRCB,January 2002 OCT 24 2 0l4age 1 of 1 <br /> 9. SPILUOVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes 0 rMIRONMENTAL HEAL i <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested 0 Q EPAR I(\RENT <br /> Test Method Developed By: 0 Spill Bucket Manufacturer 9 Industry Standard 0 Professional Engineer <br /> 0 Other(Specify): <br /> Test Method Used By: 0 Pressure F.I. Vacuum 10 Hydrostatic <br /> 0 Other(Specify): <br /> Test Equipment Used:LAKE TEST Equipment Resolution:0.0625 in. <br /> Spill Box#Tank T-1 Spill Box#Tank T-2 <br /> RUL-Fill I -Direct- PUL-Fill I-Direct- Spill Box# Spill Box# <br /> Grade level Grade level <br /> Bucket Diameter: 12.00 12.00 <br /> Bucket Depth: 15.00 15.00 <br /> Wait time between applying <br /> pressure/vacuum/water and I min 1 min min min <br /> starting test <br /> Test Start Time: 09:35:00 09:35:00 <br /> Initial Reading(Rl): 14.50 in. 13.75 in. <br /> Test End Time: 10:35:00 10:35:00 <br /> Final Reading(RF): 14.50 in. 13.75 in. <br /> Test Duration: 1 hr 1 hr <br /> (RF-RI): 0.00 in. 0.00 in. <br /> Pass/Fail Threshold or Criteria: +/-0.00 +/-0.00 +/- +/- <br /> Test Result: Pass Pass <br /> Comments-(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2319458 <br />