Laserfiche WebLink
D. Results of Testing/Servicing ` ..so <br /> Software Version Installed: TLS 250i <br /> Complete the following checklist: <br /> ®Yes ❑No * Is the audible alarm o erational? <br /> ®Yes ❑No * Is the visual alarm operational? <br /> ®Yes ❑No * Were all sensors visually inspected,functionally tested,and confirmed o erational? <br /> ❑Yes ®No * Were all sensors installed at lowest point of secondary containment and positioned so that other equipment <br /> will not interfere with their proper operation? <br /> ❑Yes ❑No * If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br /> ®N/A operational? <br /> ❑Yes ❑No * For pressurized piping systems,does the turbine automatically shut down if the piping secondary <br /> ®N/A containment monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:which <br /> sensors initiate positive shut-down? (Check all that apply) ❑Sump/Trench Sensors; ❑ Dispenser <br /> Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑Yes ❑No <br /> ❑Yes []No + For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br /> ®N/A mechanical overfill prevention valve is installed),is the overfill warning alarm visible and audible at the <br /> tank fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? <br /> % <br /> ❑Yes* ®No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment <br /> replaced and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ®Yes* ❑No Was liquid found inside any secondary containment systems designed as dry systems? <br /> (Check all that apply) ❑Product; ®Water. If yes,describe causes in Section E,below. <br /> ®Yes ❑No Was monitoring system sct-up reviewed to ensure proper settings? Attach set up reports,if applicable <br /> ❑Yes ❑No Is all monitoring equipment oerational per manufacturer's specifications? <br /> * In Section E below,describe how and when these deficiencies were or will be corrected: <br /> E. Comments: <br /> All sump censors need to he moved to low points- Need new mounting hardware and some <br /> Sensor cables, are ton short to move Found water in Waste nil sumps- Liquid was <br /> removed and contained) <br /> Monitoring System Certification Page 2 of 3 3101 <br /> SET Job#: T7 019238 <br />