Laserfiche WebLink
SAN JDANIN <br />COUNTY— <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />YRC INC <br />1535 E Pescadero Ave, Tracy <br />February 01, 2018 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />107 <br />CCR 2632(d)(1)(C) Plot plan/site map not submitted or failed to completely show where monitoring is performed. <br />An accurate UST Monitoring Site Plan was not submitted. Site map is lacking general piping layout and tank #4 <br />annular sensor was observed during inspection to be a 303 sensor. A site plan must be submitted identifying the <br />locations where monitoring will be performed. Immediately log into the California Environmental Reporting System <br />(CERS) at http://cers.calepa.ca.gov/ and upload a copy of the UST Monitoring Site Plan. <br />This is a repeat violation, Class II. <br />211 <br />CCR 2715(f)(2) Designated operator employee training not performed or log not kept. <br />The designated operator employee training for 2017 was performed but missing the hire dates for all employees <br />listed. The designated operator shall train facility employees for which he or she is responsible in the proper <br />operation and maintenance of the UST system once every 12 months. The training shall include, but is not limited <br />to: <br />1. Operation of the UST system in a manner consistent with the facility's best management practices <br />2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br />3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br />4. Name of the contact person(s) for emergencies and monitoring equipment alarms <br />Ensure that employees have been trained by the designated operator and maintain the list on site. The designated <br />operator on site during the inspection corrected the hired date and included all hire dates after July 1, 2005. <br />This was corrected on site. <br />This is a repeat violation, Class II. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 3/3/18. <br />Documents reviewed by regulator: Employee training log, designated operator monthly inspection reports, <br />monitoring plans, response plan, financial responsibility, owner/operator agreement, monitoring system <br />certification testing reports (2015, 2016, 2017), secondary containment testing reports (2016), operating permit, <br />alarm histories and alarm setup, maintenance records. <br />Documents received by operator: Routine inspection report and return to compliance certification form. <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br />Received by: Date: February 01, 2018 <br />Inspector: <br />Inspector Phone: <br />Printed Name and Title: <br />BETTY HO, EH Specialist <br />(209) 468-3455 <br />Richard Smith, Service Manager <br />FA0003854 PR0232495 SCO01 02/01/2018 <br />EHD 23-01 Rev. 10/31/2017 Page 4 of 4 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />