Laserfiche WebLink
CONE I DEME UST SER V I C63e I NC_ <br /> D!1 WORKMAN O7. 0100 MAKK"MPIKL0, CA •MZ07 Coon) •J1-i&70 <br /> AES/Systea II Precision leak Test Graph (Ov*rFill ) <br /> Invoice No. i 1289B Dotal 09/18/93 Tia* i 10t34t24 <br /> Technicians DMY Tanks 2 Tank Diameter( in) t 118 <br /> Volume (gal ) o 20000 Grade Level (in) g 153 Product Lev*1 ( in) i 151 <br /> Water Level On Tank ( in) o 0 <br /> Specific Gravitye . 75 Coefficient Of Empansione 0. 0006662 <br /> Calibration Valu*(m1 ) 1 600 Channels 2 <br /> Level Segment From& 1 To 25 Temp Segment Frost 1 To 25 <br /> Pr- oduct. I. L.. R!EG <br /> L <br /> V 5q <br /> E <br /> L .15 <br /> TO <br /> h q i„ <br /> Ra , <br /> 1_1 <br /> hd zn <br /> I <br /> T <br /> ,w <br /> 0 i. . C) 2. 0 <br /> Time-Hours.In Calibration Zone 9 Calibration Unit (gal/unit ) 0. 01760 <br /> Starting Temperature (F) e 63. 327 Head Pressure(psi (Bta) ) o 4. 09 <br /> Surface Area(sq. in) i 406. 6 Temp. Change (F/h) s 0. 016 <br /> Level volume(gph) i 0. 20 <br /> Temp. volume (gph) i 0. 21 Product Lin* (gph) a -0. 002 <br /> Net change (gph) t -0. 01 <br /> R• ss u 1 t --> 5=1A68 PIL --> PA88 <br /> Copyright (c) 1989 by AES, Inc. <br /> *e Notes ** <br /> E. F. KLUDT 6 SONS ) 1126 EAST PINE ST. I LODI CA. <br /> THIS I9 THE FINAL TWO HOURS OF A FOUR HOUR TEST. <br /> A 600 ML. CALIBRATION WAS ADDED AT THE END OF HOUR FOUR. <br />