Laserfiche WebLink
• • <br /> Tank Amperage Requirements <br /> • <br /> Tank Amperage Requirement Chart <br /> Capacity Dimensions Area Required Amperage* <br /> (Gallons) (Diameter x Length) (Sq. Ft.) (Amps) <br /> 300 38" x 60" 65.5 0.2 <br /> 560 48" x 72" 100.5 0.3 <br /> 1000 48" x 128" 159 0.5 <br /> 1000 64" x 73" 146.5 0.5 <br /> 1500 64" x 108" 195.5 0.6 <br /> 2000 64" x 144" 245.5 0.8 <br /> 3000 64" x 18' 346 1.1 <br /> 4000 64" x 24' 446.5 1.4 <br /> 4000 84" x 14' 385 1.2 <br /> 4000 96" x 10'B" 368.5 1.2 <br /> 5000 96" x 13'4" 435.5 1.3 <br /> 6000 96" x 16' 502.5 1.6 <br /> 6000 72" x 28'5" 592 1.9 <br /> 8000 96" x 21'4" 636.5 2.0 <br /> 10000 96" x 26'8" i 770.5 2.5 <br /> 10000 126" x 15'6" 684.5 2.2 <br /> • 12000 96" x 32' 904.5 2.9 <br /> 12000 126" x 18'6" 783.5 2.5 <br /> 15000 126" x 23'4" 943 3.0 <br /> 20000 126" x 31' 1196 4.3 <br /> 25000 144" x 30' 1357 4.3 <br /> 25000 126" x 38'9" 1451.5 4.6 <br /> 30000 144" x 36' 1583.5 5.0 <br /> 30000 126" x 46'6" 1707 5.5 <br /> 40000 144" x 48' 2036 6.5 <br /> 50000 144" x 60' 2488 8.0 <br /> *The suggested amperage indicated is usually sufficient for a typical tank <br /> system (tanks and piping), however, MP accepts no responsibility or <br /> liability for the selected system meeting local,state, and federal <br /> regulations regarding minimum cathodic protection on the tank system. <br /> • <br /> MATERIALS PROTECTION COMPANY P.O. Box 31354 Houston, TX 77231-1354 713/270-0952 <br />