Laserfiche WebLink
,*.. 1.: <br /> FIBERGLASS DOUBLE-WALL SUMP INSTALLATION INSTRUCTIONS <br /> r1. OPERATIONS r PERIODIC <br /> Important: Isolate All Sumps From Direct Traffic r <br /> Loading. <br /> FIGURE H-1 Fuel vapors may be present in the tank sump.To <br /> prevent fire or explosion hazard, keep all ignition <br /> sources away when removing sump enclosure lid.Treat <br /> Reinforced manhole Lid Sump Lid maintain Adequate any entry into sump area as confined space entry. <br /> Concrete Clearance <br /> • . _� 3"min. $ <br /> ys iB <br /> R gi Board <br /> (VX <br /> & - ASPHYXIATION FIRE EXPLOSION <br /> (5'X 5'X 3/4) <br /> The gasket lubricant will require periodic replacement <br /> e as it will degrade over time.Any lubricant that will <br /> ' not dissolve in gasoline or water, nor attack Buna-N <br /> rubber is acceptable. While not as long lasting, other <br /> lubricants like barium grease, or petroleum jelly can <br /> also be used. Lubricant can be applied directly to the <br /> gasket or to the inside surface of the lid flange. <br /> • The gasket is a maintenance item which will have <br /> f to be replaced periodically or when it shows a leak <br /> during a tightness test. <br /> The sump must be continuously monitored with an <br /> After backfilling to top of sump electronic leak detector for potential spills or leaks. <br /> • Backfill around sump to a level 3"above the <br /> horizontal position of the enclosed top. Place a 5'x J. RESERVOIR MONITORING <br /> 5'x 3/4"rigid board with hole on backfill to support • If the reservoir sensor indicates an alarm condition, <br /> concrete and provide a channel for water runoff it is necessary to first determine that the reservoir <br /> (see figure H-1). is level and that the alarm is not the result of an <br /> • Use a manhole large enough to allow sump lid incorrect initial fluid level setting. <br /> removal after installation. - Remove the sensor. <br /> • Adequate clearances must be maintained between - Test the sensor for proper operation. <br /> the sump lid and manhole lid to prevent the direct <br /> transfer of traffic load to the sump. Reset the fluid level in the reservoir by adding or <br /> removing fluid.The proper monitoring fluid level in <br /> • Pour slab directly onto rigid board. the reservoir is 1'F:"from the inside bottom of the <br /> • If the sump is located in a traffic area, the concrete reservoir. <br /> traffic pad, reinforcement, and thickness must be _ Reinstall the sensor and check for level. Ensure <br /> designed for job conditions and traffic loads to assure sensor is level and sitting on reservoir bottom. <br /> concrete traffic pad integrity. It is the responsibility <br /> of the tank owner or tank owner's representative to <br /> design the traffic pad for all loads. K. SUMP INSTALLATION <br /> • The Installation Checklist in this manual must <br /> be properly completed, signed by the installing <br /> contractor's representative and the tank owner's <br /> representative. <br /> • Seepage 10. <br /> 9 <br />