Laserfiche WebLink
Noe <br /> Alexia Inigues <br /> From: Aris Cacapit[EH] [acacapit@sjcehd.com] <br /> Sent: Tuesday, November 20, 2012 3:45 PM <br /> To: Alexia Inigues <br /> Cc: Katie Sommerfeld; Garrett Backus [EH]; Thuy Tran [EH] <br /> Subject: Costco Lodi Lubrizol install application update <br /> Follow Up Flag: Follow up <br /> Flag Status: Flagged <br /> Good Morning Alexia, <br /> The following was brought to my attention: <br /> Site Map C1 of 12 under General Site Development Notes: #6 "It shall be the contractor's responsibility to notify the <br /> inspector 24 hours in advance of backfilling all construction. Change 24 to 48. <br /> Site Map T4 of 12#33 lists a hydrostatic sensor-single float, Veeder-Root model#VR-794380-301. Change to <br /> hydrostatic sensor-dual float,Veeder Root model#VR-794380-303. <br /> Monitoring Plan line 490-10 change to 794380-303. <br /> The cut sheet for parts 50, 51, 52, and 53 refer to a F-Series Rigid Fiberglass Fittings for SINGLEWALL fiberglass <br /> sumps. Revise the site map T4 of 12#50, 51, 52, and 53 to include fittings for DOUBLEWALL sumps. <br /> Application for underground storage tank installation permit, page 8, section I. Monitoring,At the bottom of the interstitial <br /> space of each secondarily-contained tank, positioned as near as possible to the bottom of the tank. Manufacturer <br /> Veeder-Root Model 794380-301. Change to 794380-303. <br /> Please submit the updated documents with the requested changes. Thank you, <br /> Aris Cecapit, REHS <br /> San Joaquin County Environmental Health Department <br /> 1868 E. Hazelton Rd. <br /> Stockton, CA 95205 <br /> desk 209 468.3453 <br /> fez 209 468-3433 <br /> email acacaoit(o)sicehd.com <br /> t <br />