Laserfiche WebLink
AhN 0 6 2008 <br /> STOCKTON SERVICE STATION EQUIPMENT CO. f J�Uh(`iu. I HEALTH <br /> Q MIT/SERVICES <br /> 808 N. UNION STREET <br /> STOCKTON, CA 95205-4152 <br /> PHONE 209.464.8333 FAX 209.464.8349 <br /> LDT-890 LEAK DETECTOR TEST RECORD <br /> CUSTOMER: System Transport DATE: May 30,2008 <br /> LOCATION: 707 E.Roth Road <br /> CITY: French Camp STATE: CA ZIP: 95231 <br /> TECHNICIAN: ERIC MOLGAARD <br /> Submersible Pump Identification <br /> Manufacturer Model Serial Number <br /> RED JACKET <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> VMI <br /> Diaphragm-type <br /> Piston-type X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 32 psi (Purging Test System) <br /> 2. Gallons per hour rate 3 Gallon (Leak Test,Phase I) <br /> 3. Line pressure with pump shut off 12 psi (Leak Test Phase 1) <br /> 4. Bleed-Back Test with pump off 120 ml (Bleed-back Test) <br /> 5. Step-through time to full Dow 3 seconds (Step through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase 11)Yes X <br /> No <br /> LEAK DETECTOR TEST <br /> Note: Pass=Leak detector fids test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Form 890C <br />